📉 Voltage Drop Calculator

Work out how many volts a cable run loses, and the percentage drop, from the wire gauge, material, length, load current, and supply voltage.

Home › Voltage Drop Calculator
–
Safety note: For planning and learning only. Always follow your local electrical code (e.g. NEC) and consult a licensed electrician for real installations.

How to use the voltage drop calculator

The formula

VD = 2 × K × I × L ÷ CM

K is the resistivity constant: 12.9 for copper, 21.2 for aluminium (ohm-circular mils per foot). I is the load current in amps, L is the one-way distance in feet, and CM is the wire's circular-mil area from the standard AWG table. Percentage drop is simply VD ÷ source volts × 100.

How to use it

Pick the conductor material and size, measure the one-way run length (not out-and-back — the formula already doubles it), enter the actual load current and the supply voltage, then press Calculate.

Why it matters

Every foot of wire has resistance, so some voltage is always lost as heat along the run. Long runs on small wire are the classic problem: the tool at the far end sees much less than the panel voltage.

Example

100 ft of 12 AWG copper carrying 10 A on a 120 V circuit: VD = 2 × 12.9 × 10 × 100 ÷ 6,530 = 3.95 V, which is 3.29% — just over the 3% branch-circuit guideline. Enter exactly those values above to see it.

Frequently asked questions

What formula does this calculator use?

The standard single-phase formula VD = 2 × K × I × L ÷ CM, where K is 12.9 for copper and 21.2 for aluminium, L is the one-way length in feet, and CM is the conductor's circular-mil area. The factor 2 accounts for the round trip out and back.

How much voltage drop is acceptable?

Common guidance is no more than 3% on a branch circuit and 5% total including the feeder. Equipment may still run above that, but motors run hotter and lights dim.

Does doubling the wire size halve the drop?

Not exactly — drop falls in proportion to circular-mil area. Going from 12 AWG (6,530 CM) to 10 AWG (10,380 CM) cuts the drop by about 37%.

What about three-phase circuits?

For balanced three-phase, replace the factor 2 with √3 (about 1.732): VD = 1.732 × K × I × L ÷ CM. This calculator covers single-phase runs.

More free calculators

More Free Tool Kits

Free calculator kits from the same family — one for every trade, desk, and classroom.